文献综述
浅谈高层建筑消防给水系统摘要:为确保高层建筑消防安全,必须贯彻预防为主,防消结合的消防方针。
高层建筑的消防设计显得尤为重要,根据规范高层建筑必须设置独立的消防给水系统。
消防给水系统是高层建筑中设计的重要组成部分,考虑设计的安全性、可靠性、经济性,将影响建筑本身的安全与造价。
本文从高层建筑消防给水问题出发,分析高层建筑消防给水的设计特点以及一定的思考。
关键词:高层建筑,消防给水,给水方式Abstract: In order to ensure the fire safety of high-rise buildings, we must carry out the fire control policy of "prevention first, prevention and elimination combined".The fire-fighting design of high-rise building is particularly important. According to the regulations, the high-rise building must set up an independent fire-fighting water supply system.Fire water supply system is an important part of the design of high-rise buildings. Considering the safety, reliability and economy of the design, it will affect the safety and cost of the building itself.This paper starts from the problem of fire water supply of high-rise buildings, analyzes the design characteristics of fire water supply of high-rise buildings and some thinking.Keywords: high-rise building, fire water supply, water supply way前言:随着中国经济、社会、科技的发展,应城市化的推进,要求更多高层建筑的出现。
高层建筑为节约土体资源创造了福音,随之而来的也有许多问题。
建筑消防是首要面对的重要问题之一,通过对消防一线带来的高层建筑火灾分析,我们认识到高层建筑设计中的一些疏忽与不足,应注重给水系统的创新,结合其具体特征,为了避免给水系统中可能出现的问题的重复发生[1,2]。
一、高层建筑消防给水问题1.1超压问题超压问题在高层建筑消防设计中时常遇到,超压意味着管水压升高,超出正常值,容易造成灭火时消防水枪无法掌握;对管道及阀门有破坏,进而使管道及阀门漏水;消防使用后期时缺水等等严重危害[3],造成消防超压的原因是多方面的,比如火灾初期,消防泵启动,水泵扬程偏高,出水量小于设计值,主要特点是小流量运行下普遍出现的问题;消防给水系统分区偏大,启动泵时,为满足高层最不利需求而使底层供水压力过大等。
超压问题无法彻底解决,比如水锤超压等突发性的超压,超压其实是相对的,超过了消防给水系统的系统工作压力那就叫超压。